- Published in Isulated pipes
- Read 2219 times
- font size decrease font size increase font size
MüV type of rigid protecting pipes for electrical use
Types: MüV I. MüV II.
Application: The MÜV type of protecting pipe is applicable for protecting pipe networks of insulated conductors and cables of electric or telecommunication constructions at 1000 V alternating voltage and/or 1500 V direct voltage.
Conductors and cables are accessible at the ends of the protecting pipe.
Parts of the protecting pipe network:
Protecting pipes
Accessories (bends, sleeves)
Instructions for protecting pipe networks for electrical use:
General requirements: |
MSZ EN 61386-1 |
2008 |
Rigid protecting pipe networks: |
MSZ EN 61386-21 |
2008 |
Sizes: Instruction according to MSZ EN 60423:1999
Type |
Outer diameter (mm) |
Minimal inner diameter (mm) |
NA 12 |
12 +0;-0,3 |
9,3 |
NA 16 |
16 +0;-0,3 |
12,5 |
NA 20 |
20 +0;-0,3 |
16,5 |
NA 25 |
25 +0;-0,3 |
20,5 |
NA 32 |
32 +0;-0,4 |
27,5 |
NA 40 |
40 +0;-0,4 |
35,5 |
NA 50 |
50 +0;-0,5 |
39,6 |
Execution: Smooth surface outside and inside with round cross-section
Ovalisation: in the limits of the inner diameter
Eccentricity: max. 10% of the pipe’s diameter
Delivery length: 2 metres or as demanded to 6 metres
Material: rigid PVC for electrical use
Material properties:
Density |
gr/cm3 |
1,65 |
Tensile strength |
MPa |
min 40 |
Elongation at break |
% |
min 10 |
Impact-bending strength ( Charpy ) |
KJ/m2 |
3,5 |
Breakdown voltage |
kV/mm |
min 20 |
Specific volumetric resistance |
Ohm |
min 1012 |
Ignitability: VO – hardly inflammable
Flame proofing: it does not spread the flame, after removing the ignition flame it will be extinguished.
Specification code for MüV type of protecting pipes according to MSZ EN 50086 -1:1997
Quality properties |
Type |
|
MüV. I. |
MüV. II. |
|
1. Compression strength |
3 (medium) |
2 (substandard) |
2. Impact resistance |
3 (medium) |
2 (substandard) |
3. The smallest applicable and constructible temperature (-5°C) |
2 |
2 |
4. The highest applicable and constructible temperature (60°C) |
1 |
1 |
5. Bending strength (rigid) |
1 |
1 |
6.Electrical properties (electrical insulation property) |
2 |
2 |
7. Resistance against penetration of solid foreign objects (depending on accessory and joint) |
( 6 ) |
( 6 ) |
8. Water-proof (depending on accessory and joint) |
( 7 ) |
( 7 ) |
9. Protecting pipe of metal and compound material |
Not applicable for MüV protecting pipes |
|
10. Tensile strength (depending on accessory and joint) |
( --- ) |
( --- ) |
11.Flame proofing |
1 |
1 |
12. Suspension capacity (depending on accessory and joint) |
( --- ) |
( --- ) |
Adequacy statement of production:
"CE"- applicable: 1/98 VSZM Kft. according to government decree No. 208/1999 and 79/1997 IKIM
Certificate of type testing:
MEEI : D1459K119 CCA / HU 0091