Villamosszigetelő és Műanyaggyár Kft.

Products...

  • 1
  • 2
  • 3
  • 4
Prev Next

Plastic sleeve for MÜ I. prote…

Isulated pipes

Plastic sleeve for MÜ I. protecting pipes

Type: MÜ I Sleeve Standard: VSZM TS 06.33/2001 Application field: For join...

Plastic bent pipe for MÜV pipe…

Isulated pipes

Plastic bent pipe for MÜV pipes

Type: MÜV kö. Standard: MSZEN 50086-1:1997; MSZEN 61386-21:2008 Ap...

Plastic Profiles

Profiles and other products

Plastic Profiles

Application field: Extruded plastic profiles are developed for the building- and f...

HDPE Protective pipe for cable…

Profiles and other products

HDPE Protective pipe for cables

Standard: MSZ EN 50086 – 1, MSZ EN 50086 – 2 – 4, IEC 614, MATÁV – PKI – FI MMD 23...

Guide post to show the edge of…

Profiles and other products

Guide post to show the edge of public road

Standard: MSZ -07-3609:1981  Area of use: to show the track and edge...

MüV type of rigid protecting p…

Isulated pipes

MüV type of rigid protecting pipes for electrical use

Types: MüV I. MüV II. Application: The MÜV type of protecting pipe is applica...

MÜ III - Thin-walled flexible …

Isulated pipes

MÜ III - Thin-walled flexible plastic pipes

Type: MÜ III. Standard: VSZMTS 06.30/2001. (MSZEN 61386 except dimension...

PE-RT Wall and under-floor hea…

Hot water and heating pipes

PE-RT Wall and under-floor heating pipe

Standard: DIN 16833 : 2001, DIN 16834 : 2001, DIN 4726 : 2000 Number of ...

MÜ I - Thick walled rigid plastic pipes

Type: MÜ I.,

StandardVSZM TS 06.30/2001. (MSZ EN 61386 except dimensions)

Field of application: Applicable for protection of insulated electrical cables. Installation may be made with building into the wall or concrete by conventional technology and may be installed exposed as well. Tubes are applicable in dry, dusty, contaminated or periodically humid, hazy, vaporous or corrosive vaporous rooms having “C” and “D” classification for inflammable risk (between temperature range of (-5) °C and (+60) °C. It protects cables and tubes on the medium level of mechanical employment. The type of protection will be specified by the properties of pipe network and its accessories and the development of connections. Material: Rigid PVC for electrical use

Colour: grey or brown

Dimensions:

D = nominal diameter (mm)

v = nominal wall thickness (mm)

Description and nominal sizes of the protective pipe:

Description

D (mm)

d min. (mm)

     

MÜ I.

11

18,4

15,4

 

13,5

20,4

17,2

 

16

22,5

19,1

 

21

28,3

24,5

 

29

37

32,8

 

36

47

42,4

 

48

54

48,8

Execution: in bundles with length of 2,5 metres or according to requirements of customers.

Raw Material:

Density

g/cm3

1,65

Tensile strength

MPa

40

Elongation at break

%

15

Specific volumetric resistance at 20 °C

Ohm x cm

1 x 1015

Breakdown voltage

kV/mm

20

Execution of Product: Smooth surface outside and inside with round cross-section

Strength properties:

Flexibility: rigid

Compressive strength: on the result of 750 N compression residual flattening (max 10%), the decrease of the outside diameter is less than 25%, there is no crack on the surface

Impact resistance: After treatment at 60 ± 2 °C for 240 hours and then at -5 °C during 2 hours at least 9 from 12 test tubes will not be broken under effect of impact energy of 2 J.

Heat-resistance: 60 ± 2 °C

Ignitability: tubes are hardly inflammable according to V0 and self extinguish

Thermal expansion factor: 7x10-6 1/°C

Electrical properties:

Electrical properties: min. 100 Mohm

Electric strength: Tubes comply with requirements in case of test at 2000 V during 15 min. after immersion in water during 24 hours.

Protection from external effects:

The protective pipe is perfectly dust- and waterproof. The protective tube network with their installed accessories serves his protection according to the joint’s properties (stuffing box, joining, sticking, etc.)

 