Categories
Isulated pipes

MüV type of rigid protecting pipes for electrical use

Types: MüV I. MüV II.

Application: The MÜV type of protecting pipe is applicable for protecting pipe networks of insulated conductors and cables of electric or telecommunication constructions at 1000 V alternating voltage and/or 1500 V direct voltage.

Conductors and cables are accessible at the ends of the protecting pipe.

Parts of the protecting pipe network:

Protecting pipes

Accessories (bends, sleeves)

Instructions for protecting pipe networks for electrical use:

General requirements:MSZ EN 61386-12008
Rigid protecting pipe networks:MSZ EN 61386-212008

Sizes: Instruction according to MSZ EN 60423:1999

TypeOuter diameter (mm)Minimal inner diameter (mm)
NA 12 12 +0;-0,39,3
NA 1616 +0;-0,312,5
NA 2020 +0;-0,316,5
NA 2525 +0;-0,320,5
NA 3232 +0;-0,427,5
NA 4040 +0;-0,435,5
NA 5050 +0;-0,539,6

Execution: Smooth surface outside and inside with round cross-section

Ovalisation: in the limits of the inner diameter

Eccentricity: max. 10% of the pipe’s diameter

Delivery length: 2 metres or as demanded to 6 metres

Material: rigid PVC for electrical use

Material properties:

Densitygr/cm31,65
Tensile strengthMPamin 40
Elongation at break%min 10
Impact-bending strength ( Charpy )KJ/m23,5
Breakdown voltagekV/mmmin 20
Specific volumetric resistanceOhmmin 1012

Ignitability: VO – hardly inflammable

Flame proofing: it does not spread the flame, after removing the ignition flame it will be extinguished.

Specification code for MüV type of protecting pipes according to MSZ EN 50086 -1:1997

Quality properties

Type

 

MüV. I.

MüV. II.

1. Compression strength

3 (medium)

2 (substandard)

2. Impact resistance

3 (medium)

2 (substandard)

3. The smallest applicable and constructible temperature (-5°C)

2

2

4. The highest applicable and constructible temperature (60°C)

1

1

5. Bending strength (rigid)

1

1

6.Electrical properties (electrical insulation property)

2

2

7. Resistance against penetration of solid foreign objects (depending on accessory and joint)

( 6 )

( 6 )

8. Water-proof (depending on accessory and joint)

( 7 )

( 7 )

9. Protecting pipe of metal and compound material

Not applicable for MüV protecting pipes

10. Tensile strength (depending on accessory and joint)

( — )

( — )

11.Flame proofing

1

1

12. Suspension capacity (depending on accessory and joint)

( — )

( — )

Adequacy statement of production:

“CE”- applicable: 1/98 VSZM Kft. according to government decree No. 208/1999 and 79/1997 IKIM

Certificate of type testing:

MEEI : D1459K119 CCA / HU 0091

Scroll to top