Categories
Supporting, crossover and connecting insulator

Supporting insulators with a nominal working voltage over 1kV

Types: ETA 12, ETB 12, ETC 12, ETB 24-1, ETB 24-2, ETB 40, ETC 40

Standard: MSZ IEC 273, MSZ EN 60 660, VSZM TS 51-86

Application field: For indoor or outdoor application at nominal voltage range above 1 kV

Material: Epoxy casting resin filled with silica flour (for indoor application)

Colour: red (for indoor application)

According to requirements we can produce insulators made of cyclo-alyphatic epoxy casting resin system for outdoor application as well. Insulators for outdoor use are unpainted or they can be coloured according to agreements.

Dimensions and shaping: for example: ETB 12

Typical technical data (Description)

 

ETA 12-1

ETA 12-2

ETB 12-1

ETB 12-2

Product number

MÖ 2801

MÖ 2801/a

MÖ 3428

MÖ 3428/a

Nominal voltage

kV

12

12

12

12

Test voltage at industrial frequency

kV/1′

28

28

28

28

Impulse test voltage

kV

75

75

75

75

Nominal leaking path*

mm

200

200

200

200

Minimum bending crumbling force at 20 °C

N

3750

3750

7500

7500

Dimension:

diameter of the bottom

mm

70

70

84

84

diameter of the head-piece

mm

56

56

70

70

Height

mm

130

130

130

130

Number of ribs

db

3

3

3

3

Size of the metal cast inserted into the bottom

 

M 16

M 16

M 20

M 20

Size of the metal cast inserted into the head

 

M10

M6

M16

M10

Number of the metal cast inserted into the head

db

1

2

1

2

Nominal mass of the insulators

kg

0,6

0,6

0,95

0,95

Thread start of the metal cast*

mm

12

12

15

15

VEIKI standard inspection report number

1064/VBF

1064/VBF

921/VBF

921/VBF

Typical technical data (Description)

 

ETC 12-1

ETC 12-2

ETB 24-1

ETB 24-2

Product number

ÖF 5593

ÖF 5593/a

MÖ 3476

MÖ 3476/a

Nominal voltage

kV

12

12

24

24

Test voltage at industrial frequency

kV/1′

28

28

50

50

Impulse test voltage

kV

75

75

125

125

Nominal leaking path*

mm

200

200

340

340

Minimum bending crumbling force at 20 °C

N

12500

12500

7500

7500

Dimension:

diameter of the bottom

mm

104

104

92

92

diameter of the head-piece

mm

90

90

70

70

height

mm

130

130

210

210

Number of ribs

db

3

3

7

7

Size of the metal cast inserted into the bottom

 

M20

M20

M20

M20

Size of the metal cast inserted into the head

 

M16

M10

M16

M10

Number of the metal cast inserted into the head

db

1

2

1

2

Nominal mass of the insulators

kg

1,5

1,5

1,6

1,6

Thread start of the metal cast*

mm

10

10

15

15

VEIKI standard inspection report number

1041/VBF

1041/VBF

754/VBF

754/VBF

Typical technical data (Description)

 

ETB 40,5-1

ETB 40,5-2

ETC 40,5-1

ETC 40,5-2

Product number

MÖ 3477

MÖ 3477/a

MÖ 4640

MÖ 4640/a

Nominal voltage

kV

40,5

40,5

40,5

40,5

Test voltage at industrial frequency

kV/1′

80

80

80

80

Impulse test voltage

kV

190

190

190

190

Nominal leaking path*

mm

600

600

600

600

Minimum bending crumbling force at 20 °C

N

7500

7500

12500

12500

Dimension:

diameter of the bottom

mm

107

107

127

127

diameter of the head-piece

mm

70

70

90

90

height

mm

360

360

360

360

Number of the ribs

db

14

14

15

15

Size of the metal cast inserted into the bottom

 

M24

M24

M30

M30

Size of the metal cast inserted into the head

 

M16

M10

M16

M10

Number of the metal cast inserted into the head

db

1

2

1

2

Nominal mass of the insulators

kg

3,3

3,3

5,4

5,4

Thread start of the metal cast*

mm

20

20

20

20

VEIKI standard inspection report number

1024/VBF

1024/VBF

1025/VBF

1025/VBF

Products have been tested and approved by VEIKI (Hungarian Institute for Research of Electric Power Industry).

Execution: In carton

Scroll to top